Place of Origin: | China |
---|---|
Brand Name: | Zion communication OR OEM |
Certification: | CE, RoHS, VDE, UL, CUL, LPCB |
Model Number: | Fire Risistant Cable Unshielded 2 Cores |
Minimum Order Quantity: | 20 KM |
Packaging Details: | 100M, 200M, Roll, Carton |
Delivery Time: | 25 working days |
Payment Terms: | T/T, L/C |
Supply Ability: | 1000KM / Month |
Conductor: | Solid Bare Copper | Insulation: | Silicone Rubber |
---|---|---|---|
Jacket: | FRHF PVC | Color: | Orange |
Package: | 100M, 200M, Roll, Carton | ||
Highlight: | fire alarm cable,fire resistance cable |
Unshielded 2 Cores 0.75mm2 FRHF Fire Risistant Cable for Connecting Fire Alarms
Quick Detail:
Description:
KT1404 FRHF Unshielded 2 Cores Fire Resistant Cable Bare Copper Silicone Insulation
is a specific type of fire alarm cable Produced by Zion communication. These cables are used for
installation in fire systems for connecting fire alarms etc. The cable can be installed
in dry and moist areas as well for fixed open air installation. This cable type with
electrostatic screening (St) protects the transmission circuits against extern-electrical
interferences. And all these cables comply to:
IEC60331-23-2003
IEC60332-3-22-2005
IEC61034-2-2005
EC60754-1-99
IEC60754-2-99
IEC60331-21:1999
BS EN 61034-2:2005
BS 7629-1:2008
BS EN 50267-2-1:1999
Zion communication using best raw material and best worker to produce КПС нг(А)-FRHF
Unshielded 2 Cores to meet high performance in practical application. КПС нг(А)-FRHF
Unshielded 2 Cores is packed in 200m Roll, 2 Rolls in Carton, then will be layed on
pallet to protect the spool and easier carry.Because of good managing methods,
Zion communication’S price of КПС нг(А)-FRHF Unshielded 2 Cores is not high although
our quality is really high.
Applications:
These cables are used for installation in fire systems for connecting fire alarms etc.
The cable can be installed in dry and moist areas as well for fixed open air installation.
This cable type with electrostatic screening (St) protects the transmission circuits
against extern-electrical interferences.
KT1404 FRHF Unshielded 2 Cores Fire Resistant Cable Bare Copper Silicone Insulation | |||||
APPLICATION: | |||||
These cables are used for installation in fire systems for connecting fire alarms etc. The cable can be installed in dry and moist areasas well for fixed open air installation. This cable type with electrostatic screening (St) protects the transmission circuits against externelectrical interferences. |
|||||
Standards: | |||||
All these cables comply to: | |||||
IEC60331-23-2003 IEC61034-2-2005 IEC60754-2-99 |
IEC60332-3-22-2005 IEC60754-1-99 IEC60331-21:1999 |
BS 7629-1:2008 BS EN 61034-2:2005 BS EN 50267-2-1:1999 |
|||
Fire Testing: | |||||
180 minutes under fire of 750 degrees without short-circuit. | |||||
ELECTRICAL DATA (AT20OC): | |||||
Minimum Bend Radius |
Min.Insulation resistance |
Max.Working Temperature |
Test voltage (rms value) |
Max. Operating voltage peak value |
|
MΩ/km | ℃ | V | V | ||
8×Diameter | 200 | -15℃~+90℃ | 1000 | 300 | |
TYPES AND MECHANICAL DATA: | |||||
Types sqmm (mm2) |
Conductor BC (mm) |
Insulation | Level of twisting |
Jacket Matterial | OD of Jacket (mm) |
2×0.22 | 1×2×0.50 | Silicone | FRHF | 4.10 | |
2×0.5 | 1×2×0.76 | Silicone | FRHF | 5.00 | |
2×0.75 | 1×2×0.94 | Silicone | FRHF | 5.90 | |
2×1.0 | 1×2×1.07 | Silicone | FRHF | 6.30 | |
2×1.5 | 1×2×1.35 | Silicone | FRHF | 6.90 | |
2×2.5 | 1×2×1.70 | Silicone | FRHF | 8.00 | |
*Notes | Class 1:Solid | BC: | Bare Copper | ||
Order Informations: | |||||
Marking |
Zion communication KT1400 FRHF 2×***MM2 CABLE |
||||
Package | 100M, 200M, Roll, Carton, Pallet | ||||
More info. | Please contact with us. |
Competitive Advantage:
1, From raw materials to final products, we perform intense quality checks to maintain our product quality:
A, Incoming material inspected by QC.
B, Manufacturing Process Control
C: Workers trained daily/weekly/monthly
D: Work instructions manual at each work station
E: 5S system implemented
F: Machine maintenance procedure
G: Quality Control and Final Inspection
The QC staff will check the material, process product
and final product according to the specification or test procedure.
2, Our R&D efforts center on reinforcing and developing element technologies
needed to support the future growth and success for customers and Zion communication.
3, We know customers have urgent needs.
We are skilled at effective communication to interact with customers.
In order to provide prompt service, we can answer for you 7*24 hours.
4, We can Quickly and professionally answer for the inquire
5, More than 1000 kinds of cable, connectors and assembles can be produce and organized from us
6, Intime delivery